Correlux P2 Leak Noise Correlator
|
Technical Data
|
|
Correlux P-2
|
|
Processor
|
RISC- und DSP-
processor
|
|
Display
|
320 x 240 Pixel, 0.25" VGA monochrome
|
|
Data entry
|
Rotary encoder with enter
function
|
|
Power supply
|
Internal Akku, NiMH,
external 12 V DC (car- adapter), 100- 240 V AV
|
|
Operating- / charging time
|
> 18 h / < 3 h
|
|
Interface
|
RS 232 (updates, print out
and data communication via PC)
|
|
Connections
|
Sensor/ Hydrophone direct connection,
antenna, headphones/ recharging, charging contacts in case
|
|
Protection class
|
IP 67
|
|
Operating temperature
|
-20 °C ... +60 °C
|
|
Dimensions/ weight
|
270 x 130 x 240 mm / 3.3 kg
|
|
Transmitters TR A/ TR B
|
|
Display
|
LCD, 2 x 16 characters
|
|
Readout
|
Battery state, noise level, system state
|
|
Buttons
|
On/ Off, lighting, volume
|
|
Radio frequency
|
433 MHz
|
|
Transmitter power
|
<500 mW
|
|
Operating- / charging time
|
> 18 h / < 3 h
|
|
Power supply
|
Internal Akku, NiMH,
external 12 V DC (car- adapter), 100- 240 V AV
|
|
Connections
|
Sensor, antenna, headphones
|
|
Protection class
|
IP 67
|
|
Operating
temperature
|
-20 °C ... +50 °C
|
|
Dimensions/ weight
|
190x134x180mm bei
1,7kg
|
Sensors PAM CORR |
|
Sensors PAM CORR
|
Piezo sensors with active
amplifier
|
|
Adapter
|
Magnet adapter
|
|
Operating temperature
|
-20 °C ... +80 °C
|
|
Dimensions/ weight
|
38 x 78 mm / 0.4 kg
|
Functional description
The correlator Correlux P-2 is used for leak location on pipes for potable water. Water, escaping from a leak under pressure creates a noise which travels into both directions of the pipe. This noise is recorded by two sensors (piezo- microphones, hydrophones) attached to the pipe ( e. g.: valves, hydrants), amplified and transmitted to the correlator. The Correlux P-2 compares both signals (correlation) and calculates the exact distance to the leak by use of the signal delay, the sensor distance and the sound velocity.
- Easy handling with rotary encoder
- Rugged and compact design
- Simultaneous display of the correlation chart and the coherence spectrum (FFT- analysis)
- Quick filter optimisation without using menus
- Fast and easy leak identification by using the overview measurement with unknown pipe parameters
- High radio output for broad reach
- Transmitter and correlator with direct headphones plug-in to listen live to the leak noise
- Recharging the complete system in the closed case – direct charging is possible, too
- Up to 6 pipe sections measurable
- Active piezo ceramics accelerometers, best suited for plastic pipes
- Automatic and manual filter adjustment 0 ... 4000 Hz
- Reliable measurement results
- Easy to use
- Optimised for plastic pipes
- Long operating time
- Sensor can be connected to the central unit
- Sturdy housing
Scope of Delivery
Correlux P-2 |
P2 Basic |
P2 Standard |
P2 Pro |
DK P2 Correlator |
X |
X |
X |
TR A transmitter + sensor |
X |
X |
X |
TR B transmitter + sensor |
|
X |
X |
Headphones |
X |
X |
X |
Ground microphone |
|
|
X |
Transportation case |
Option |
X |
X |
Recharger |
X |
X |
X |
Hydrophone |
Option |
Option |
Option |
Vehicle charger |
Option |
Option |
Option |
Software |
|
|
|
Listening mode |
|
|
X |
Chart memory |
|
X |
X |
PC software |
|
X |
X |
|